当前位置:深圳市华伦康盛科技有限公司>>日本横河>>DCS卡件>> AAP135-S53日本横河DCSAAP135-S53脉冲输入模块-DCS系统
产地 | 进口 | 加工定制 | 否 |
---|
日本横河DCSAAP135-S53脉冲输入模块日本横河DCSAAP135-S53脉冲输入模块
信号类型 横河
卡件型号 通道数 说明
AI AAI135-H03 8 通道隔离,支持HART协议、G3标准 协议
AAI835-H03 4in/4out 通道隔离,支持HART协议、G3标准
AI AAI143-H03 16 卡件与现场隔离,但通道不隔离,支持HART协议、G3标准
AAR145-S03 16 通道隔离,支持G3
AAT145-S03 16 通道隔离,支持G3
AAP135-S03 8 通道隔离,支持G3
ADV159-P01 32 通道隔离,支持G3
ADR154-P03 16 继电器输出,支持G3标准
ADR154-P03 16 继电器输出,支持G3标准
ADV151-E13 32 卡件与现场隔离,16点一个公共端,支持G3标准,1ms
| Items | Specifications | |
| Model | AAP135 | |
Number of input channels | 8, isolated channels | ||
|
| 2-wire type: Contact ON/OFF, voltage pulse, current pulse | |
Input signal (*3) | (possible to supply transmitter power supply) | ||
|
| 3-wire type: Power-supply-type voltage pulse | |
Input frequency | 0 to 10 kHz (*4) | ||
Withstanding voltage | Between input and system: 500 V AC, For 1 minute | ||
Between channels: 500 V AC, For 1 minute (*1) | |||
|
| ||
Minimum input pulse width | 40 μs | ||
|
| Contact input | |
|
| Open/close levels of relay contact and transistor contact | |
|
| Open: 100 kΩ or more, Close: 200 Ω or less | |
|
| Contact capacity | |
|
| When supplying 12 V DC: 15 V DC 15 mA or more | |
Input signal level | When supplying 24 V DC: 30 V DC 30 mA or more | ||
|
| Voltage/current pulse input (Current input is converted to voltage.) | |
|
| VH (high level): 3 to 24 V DC | |
|
| VL (low level): -1 to 8 V DC | |
|
| VH-VL (swing value): 3 V or more | |
|
| Signal source resistance: 1 kΩ or less | |
Shunt resistance | Can be selected from none/200/500/1000 Ω. | ||
(Open when power is OFF and for the standby side in a dual-redundant configuration) | |||
|
| ||
Pull-up resistance | 68 kΩ (12 V DC or 24 V DC) | ||
Filter |
| Filter for eliminating chattering can be set. (*2) | |
Data update period | 2 ms | ||
Transmitter power supply | Can select 24 V DC/12 V DC. | ||
Limiter value 12 V DC ±10 %: 40 mA, 24 V DC ±10 %: 30 mA | |||
|
| ||
Maximum current consumption | 300 mA (5 V DC), 400 mA (24 V DC) | ||
Weight |
| 0.3 kg | |
External connection | Pressure clamp terminal, KS cable, MIL connector cable | ||
*1: | The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable. | ||
*2: | When the pulse input signal is dry contact (such as from a mechanical relay) up to 10 Hz, it is possible to eliminate the | ||
| chattering. |
| |
*3: | The connection method of the field devices varies depending on the input signal. | ||
| For details, please refer to “Installation Guidance (TI 33Q01J10-01E).” | ||
*4: | Input frequency is 0 to 800 Hz to receive no-voltage contact signals between terminal B and C. |
请输入账号
请输入密码
请输验证码
以上信息由企业自行提供,信息内容的真实性、准确性和合法性由相关企业负责,仪表网对此不承担任何保证责任。
温馨提示:为规避购买风险,建议您在购买产品前务必确认供应商资质及产品质量。