为了正确选择自动控制阀的通径,用户需要了解下列事项: To properly size an automatic control valve you need to know the following: - Z和Z低的进口压力
HighestLowest inlet pressures - 出口压力
Outlet pressure - Z大流量要求
Maximum flow requirements - Z小流量要求
Minimum flow requirements
步骤1:利用流量表,并且在横轴上找出符合用户Z大流量要求的流量值。 Step 1: Utilize the high flow chartthe flow as found on the horizontal axis which corresponds with your maximum flow requirements. 步骤2:从这一点划垂线,延伸到与相应的Z小压差的水平线相交。(此时,Z小压差将是Z低进口压力减去所需要的出口压力,这也就是所说的∆P。) Step 2: From this point draw a vertical line until you intersect with the horizontal line corresponding with the minimum differential pressure. Your minimum differential pressure will be the lowest inlet pressure minus the desired outlet pressure, this is also known as the delta P. 步骤3:从这一点向右移动直到*个阀门的通径线。这就是在25英尺/秒间歇流量时应该采用的Z小阀门通径。如果Z大流量是连续的,那么不要超过Z大连续流量表上所列的美制加仑/分钟(20英尺/秒)。 Step 3: From this point move right to the first valve size line. This will be the minimum valve size which should be used on intermittent flow of 25 ft./sec. If maximum flow is continuous, then do not exceed the GPM 20 FT./sec. listed on the maximum continuous flow table. | | 步骤4:利用流量表,在竖轴上找到Z大压差。(用户的Z大压差将是Z进口压力减去所需要的出口压力,这也就是所说的∆P。) Step 4: Utilize the flow chartthe maximum differential pressure as found on the vertical axis. Your maximum differential pressure will be the highest inlet pressure minus the desired outlet pressure, this is also known as the delta P. 步骤5:从这一点划水平线与步骤3选择的阀门通径相应的线相交。 Step 5: From this point draw a horizontal line until you intersect with the line corresponding to the valve size as selected in step 3. 步骤6:从这一点划垂线向下与横轴相交。这就是以这些变量为基础的阀门的Z小流量能力。 Step 6: From this point draw a vertical line down to the horizontal axis. This will be the minimum flow capabilities of the valve based on these variables. 注意:1 如果通过步骤6得到的Z小流量能力比用户实际的Z小流量要求,则用户应该考虑采用并联安装方式。采用这个Z小流量能力,从步骤1开始选择用户需要的用于低流量旁路的通径。 2 采用空穴图表并且确定进口和出口压力的相交是否落在阴影区域内。如果是,用户应该考虑串联安装方式。两个阀门都应该按照上述步骤选择通径。 Notes: 1 If the minimum flow capability obtained from step 6 is above your actual minimum flow requirements, you should consider a parallel installation. Using the minimum flow capability, begin at step 1 to the size you will need for this low-flow by-pass. 2 Use the cavitation chartdetermine if the intersection of the inletoutlet pressures falls in the shaded area. If so, you should consider a series installation. Both valves should be sized in accordance with the above steps. |