FA1761F/FA3861F      USER’S GUIDE                           P.0   

                      Table of contents

General description--------------------------------------------------------------------1                                                                            

■FA1761F--------------------------------------------------------------------------------------1                                                                                               

■FA3861F--------------------------------------------------------------------------------------1

Common specifications--------------------------------------------------------------1

Dimension of FA1761F----------------------------------------------------------------2

Dimension of FA3861F----------------------------------------------------------------2

Installation ---------------------------------------------------------------------------------2

Illustration of front panel----------------------------------------------------------- 3 

Installation place----------------------------------------------------------------------- 4

Installation method------------------------------------------------------------------------------- 4

Power line and ground connections ----------------------------------------- 4

ON/OFF output and PID control output connections----------------- 5

Communication connections----------------------------------------------------- 5

Initial set------------------------------------------------------------------------------------ 6

Key functions in running------------------------------------------------------------ 6

Over temp. display----------------------------------------------------------------------7

Under temp. display--------------------------------------------------------------------7

ON/OFF of key-lock---------------------------------------------------------------------7

Auto-tuning---------------------------------------------------------------------------------7

PID control display---------------------------------------------------------------------7FA1761F/FA3861F      USER’S GUIDE                           P.1 

General description

The FA1761F/FA3861F is a temperature- humidity controller for the dry/wet bulb system without transducer 

FA1761F

Name   Temperature controller

Model   FA1761FRecorder output include

Input    Pt100Ω

Accuracy±0.3

Setting rangeSCLL -99.0~0.0

SCLH 10.0~200.0

Display range-99.9~210.0

FA3861F

Name   Humidity controller

Model   FA3861FRecorder output include

Input    Pt100Ω

Accuracy±1

Setting rangeSCLL 0.0~40.0

SCLH 60.0~100.0

Common specifications

DisplayPV   8 red  LED

SV   8 green  LED

7 segments4 character positions

Display cycle1 sec.

ControlPIDSSR + ON/OFF + ON/OFF

Output PID outputSSR 

ON/OFF outputrelay contact output

Action modereverselow/directhigh

Proportional band0.0~50.0/

Integral time0~99min.59 sec.

Derivative time0~99min.59sec.

Control cycle1~30 sec.

Hysteresis of alarm0.1~ 2.5/

Deviation setting±30.0/

Recorder outputSCLL~SCLH──DC 4~20mA

Power voltageAC100 / 110V ±10or

AC200 / 220V ±10 50 / 60Hz    4VA

Memory backupapprox.10 yearsat 23±255±10RHfor standard model

Dimensions:(H96 W48 D129

Panel cutout:(H90±0.5  W43±0.5

Weightapprox.500g

Standard Accessorymounting 2pcs/1set

FA1761F/FA3861F      USER’S GUIDE                           P.2

Dimension of FA1761F

Dimension of FA3861F

Installation

■1 set       ■N sets

FA1761F/FA3861F      USER’S GUIDE                           P.3

Illustration of front panel

 

(1) 4 character red LEDDisplay of PVWhen we want to key-in a valuethe position glittered with this value. If displayHHHHit means the present valuePVis higher than SCLH If displayLLLLit means the present valuePVis lower than SCLL            

(2) 4 character green LEDDisplay of SVWhen we want to key-in a valuethe position glittered with this value.SV and percent of PID output are changeable              

(3) Display of output1Light lamped when output1 is ON

(4) Display of output2Light lamped when output2 is ON

(5) Display of output3Light lamped when output3 is ON

(6) Display of communicationIt’ll check automatically once every second.Communicate status between FA1761F and FA3861F),if the status is OKit glittered with lamp

(7) Function keyWe can change the display mode by pressing this key

(8) Left keyFor input position moving

(9) Up keyIncrease value or function select

(10) Down keyReduce value or function select

(11) UnitTemperatureFA1761F-HumidityFA3861F-﹪。

FA1761F/FA3861F      USER’S GUIDE                           P.4

Installation place

■Place where an ambient temperature is 0 to 40℃,and relative humidity is 80﹪RH or less。

■Place where no water splash and non-condensing develop

■Place where no direct sunshine exist

■Place where is clear and dust or corrosive gas are not present

■Place where is far from noise-generating devices such as heavy duty solenoid switches and phase control SCRs

Installation method

■Insert the FA1761F/FA3861F unit from through the cutout on the panel

■Secure two claws of the mounting brackets to the holes on the side panel of the unit

■Tighten the screws for the mounting brackets to secure the units

Power line and ground connections

■The power line and ground connections are made at the FA1761F/FA3861F’s terminal board

■The FA1761F/FA3861F is designed to operate on 100/110VAC or 200/220VAC 50/60Hz power line

■Make sure to connect the G(ground)terminal to the earth to minimize external interference。

■For  AC100V or AC110V       ■For  AC200V or AC220V

FA1761F/FA3861F      USER’S GUIDE                           P.5

ON/OFF output and PID control output connections

Communication connections

FA1761F/FA3861F      USER’S GUIDE                           P.6

Initial set

This item contains setting range selectionoffset adjustaction mode selectionreverse or direct)。

The initial set display is shown from the normal display by simultaneously pressing the two  keys    and    for a whileat the same timePID outputOFF

Under this statusIt will change by pressing    key in sequence as below

Display

Name

Function

SCLL

Scale Low

The low limit value of setting for Temp. or Humi.

SCLH

Scale High

The high limit value of setting for Temp. or Humi.

oFFS

Offset Adjust

Range±5.0

ExampleIf deviation value+1input value-1

cycL

Cycle Time

Range1~30 sec.

LMTL

Limit Low

The low limit value of PID output

Range0~30

LMTH

Limit High

The high limit value of PID output

Range70~100

PID

PID Zone

The cut point of PID zone(2 parts)

SEt

Set Method

AbSo(Absolute)/DeviationdEU1 selection of output2 and output3

oPEr

Operate Mode

cont(Control)/ALAr(Alarm) selection of output2 and output3

out1

Out1

HigH(High)/Louu(Low) selection of output1

out2

Out2

HigH(High)/Louu(Low) selection of output2
When operate modeAlarmit decided automatically

out3

Out3

HigH(High)/Louu(Low) selection of output3
(When operate mode=Alarm,it decided automatically)

uuEt

Wet

Temperature display of wet bulb

Loc

Loc

Lock function selection

tyPE

Type

Display of controller’s model

Key functions in running

Green LEDIt will change by pressing    key in sequence as below(In running)
Set1Pb LIt Ldt LPb HIt Hdt HSet2diF2SEt3diF3

FA1761F/FA3861F      USER’S GUIDE                           P.7

Display

Name

Function

SEt1

Set 1

Setting of output1

Pb L

Proportional Band Low

Setting of P(Low)

It L

Reset Time Low

Setting of I(Low)

dt L

Reset Time Low

Setting of d(Low)

Pb H

Proportional Band High

Setting of P(High)

It H

Reset Time High

Setting of I(High)

dt H

Reset Time High

Setting of d(High)

SEt2

Set 2

Setting of output2

diF2

Differential Gap2

Hysteresis of output2

SEt3

Set 3

Setting of output3

diF3

Differential Gap3

Hysteresis of output2

■ Setting range of P0.0~50.0 deg / ﹪。

■ Setting range of I and D0.00~99.59(0~99min.59sec.)

■ Setting range of differential gap0.1~2.5 deg / ﹪。

Over temp.display

It will show the error message as belowHHHH at the same time,PID output=OFF。

Under temp.display

It will show the error message as belowLLLL at the same time,PID output=OFF。

ON/OFF of key-lock

We can change the key lock ON/OFF from the normal display by simultaneously pressing the two  keys   and    for a while

Auto-tuning

We can change the auto-tuning ON/OFF from the normal display by simultaneously pressing the two  keys   and    for a while

PID control display

We can change the setting value/percent of PID output from the normal display by simultaneously pressing the two  keys   and    for a while

免责声明

  • 凡本网注明“来源:仪表网”的所有作品,均为浙江兴旺宝明通网络有限公司-仪表网合法拥有版权或有权使用的作品,未经本网授权不得转载、摘编或利用其他方式使用上述作品。已经本网授权使用作品的,应在授权范围内使用,并注明“来源:仪表网”。违反上述声明者,本网将追究其相关法律责任。
  • 本网转载并注明自其他来源(非仪表网)的作品,目的在于传递更多信息,并不代表本网赞同其观点和对其真实性负责,不承担此类作品侵权行为的直接责任及连带责任。其他媒体、网站或个人从本网转载时,必须保留本网注明的作品第一来源,并自负版权等法律责任。
  • 如涉及作品内容、版权等问题,请在作品发表之日起一周内与本网联系,否则视为放弃相关权利。
联系我们

客服热线: 15267989561

加盟热线: 15267989561

媒体合作: 0571-87759945

投诉热线: 0571-87759942

关注我们
  • 下载仪表站APP

  • Ybzhan手机版

  • Ybzhan公众号

  • Ybzhan小程序

企业未开通此功能
详询客服 : 0571-87759942